TBP-0-4.6,TBP-O-4.6,TBP-0-7.6,TBP-O-7.6,TBP-A-7.6/131,TBP-B-7.6/131,TBP-C-7.6/131,TBP-A-7.6/85,TBP-B-7.6/85,TBP-C-7.6/85,TBP-A-10.5/131,TBP-B-10.5/131,TBP-C-10.5/131,TBP-A-10.5/85,TBP-B-10.5/85,TBP-C-10.5/85,TBP-A-12.7/131,TBP-B-12.7/131,TBP-C-12.7/131,TBP-A-12.7/85,TBP-B-12.7/85,TBP-C-12.7/85,TBP-B-42/200,TBP-C-47/200,TBP-B-42F/310,TBP-C-42F/310,TBP-A-7.6F,TBP-B-7.6F,TBP-C-7.6F,TBP-A-10.5F,TBP-B-10.5F,TBP-C-10.5F,TBP-A-12.7F,TBP-B-12.7F,TBP-C-12.7F,TBP-B-42F,TBP-C-42F,TBP-B-12.7/131-J,TBP-B-12.7/85-J,TBP-B-12.7/J, TBP-B/F-10.5组合式过电压保护器,TBP-B/F-12.7
JBP-HY5CD2-12.7/41×29过电压保护器试验方法
按原理图将相关仪表和设备连接好。测试前应*先将电流继电器LJ的整定值调至*小值(作为后备保护),然后将试验变压器空载升压,电流继电器LJ应不动作,将数字电流表A2的量程调至10~20A(5KVA及以下容量试验变压器可不加限流电阻R)。
工频试验电压分别加在JBP-HY5CD2-12.7/41×29过电压保护器的A和D、B和D、C和D、A和C、B和C、以及A和B上,缓慢调高试验变压器的输出电压,同时观察电压表及数字电流表A2,TBP间隙未击穿放电时,数字电流表A2的读数为零或数值很小。当试验变压器的输出电压达到JBP-HY5CD2-12.7/41×29过电压保护器的动作值时,JPB间隙被击穿放电,数字电流表A2的读数将突增,电流表A1同样也会有突变现象产生,此时试验变压器的高压输出电压值即为该JBP-HY5CD2-12.7/41×29过电压保护器的工放值。
JBP-HY5CD2-12.7/41×29过电压保护器安装及接线方法
a、户内型过电压保护器可以水平安装在各种不同型号的开关柜内,该类产品除直接与开关柜"A"、"B"、"C"三相及接地相("D"相)相连的线鼻子为裸导体外,其余部分被绝缘体封闭,因此它的相间、相对地(或柜体)的距离及对柜体安装空间要求相应较小,可直接安装在开关柜的手车底盘内或互感器室内;
b、带有过电压动作计数器的JPB过电压保护器,先将JPB过电压保护器本体(安装方式同上)和过电压动作计数器各自固定好后,通过配备的特制电缆相连,安装尺寸详见《过电压动作计数器说明书》。